DISTRIMAT poles

DISTRIMAT power poles

Polygonal galvanised steel poles for overhead distribution lines, 8 to 16 m and 180 to 4,400 daN.

Technical specifications

Section Octagonal (8 sides) or polygonal (12 sides), equal strength in every direction
Range heights 8 to 16 m
Nominal load 0.25 m below top 180 to 4,400 daN by reference
Construction Single piece up to 11.9 m; above, two sections slip-jointed on site
Steel Grade S500 to EN 10025 (500 MPa yield strength)
Welding Longitudinal submerged-arc (SAW)
Galvanising Hot-dip to ISO 1461, zinc > 70 µm inside and outside
Safety factor Above 1.8 relative to yield strength
Standard fittings Top cap, standard holes, rung brackets, name plate, earthing nut, bitumen protection

Dimension table

Item codeH (m)Load at 0.25 m (daN)Base Ø (mm)Top Ø (mm)SidesUnits / 40' container
D0802000808200117808380
D0803300808330152808289
D0804900808490189808196
D0806500808650220808169
D0807500808750243808144
D08092010289202741028100
D081170102811702681028100
D08150010281500322102881
D0901800809180117808380
D0902900809290152808289
D0904400809440189808196
D0905700809570220808169
D0906700809670243808144
D09080008098002741028100
D091020080910202681028100
D09133008091330322102881
D091580080915802801028100
D10026008010260152808289
D10039008010390189808196
D10051008010510220808169
D10059008010590243808144
D100720102107202741028100
D100920102109202681028100
D101200102101200322102881
D101400140101400280140881
D101840140101840322140864
D103300180103300448180836
D11023008011320152808270
D11035008011350189808196
D11046008011460220808169
D11054008011540243808144
D110650102116502741028100
D110820102118202681028100
D111060102111060322102881
D111260140111260280140881
D111650140111650322140864
D113000180113000448180836
D12021008012210152808270
D12032008012320189808196
D12043008012430220808169
D12050008012500243808144
D120600102126002741028100
D120760102127602681028100
D12099010212990322102881
D121160140121160280140881
D121520140121520322140864
D1227601801227604501801236
D1234401801234404501801236
D13046010213460264 / 122113 / 1028100
D13046010213520254 / 123116 / 1028100
D13065010213650280 / 122113 / 1028100
D13072008013720305 / 127118 / 102881
D13090010213900273 / 124114 / 1028100
D131060102131060306 / 125114 / 102881
D131250140131250312 / 161149 / 140864
D121160140131390345 / 165154 / 140864
D121520140131550365 / 167154 / 1401249
D122760180131875420 / 175164 / 1401236
D123440180132300465 / 178163 / 1401236
D120210080132550460 / 237224 / 2001236
D122760180134400562 / 246225 / 2001225
D14040010214440156 / 131121 / 1028100
D14054010214540250 / 130120 / 1028100
D14065010214650296 / 138127 / 102881
D14065010214940290 / 138131 / 102881
D140650102141000300 / 140127 / 102881
D141100140141100302 / 170160 / 140864
D141100140141350348 / 180172 / 1401249
D141100140141440400 / 205190 / 1401249
D141100140141750430 / 195179 / 1401236
D141100140142000446 / 146181 / 1401236
D142350200142350405 / 246230 / 2001236
D142350200142780440 / 246230 / 2001225
D142350200143000480 / 260244 / 2001225
D142350200144000540 / 2672001225
D16080010216800300 / 140127 / 102881
D161251140161250430 / 195179 / 1401236
D191620140161620446 / 196181 / 1401236
D162510200162510480 / 260244 / 2001225

Key : For two-section poles (13 m and above), diameters are given for each section (bottom / top). Manufacturing tolerances and setting-depth formulas available on request.

Applications

  • Medium and low voltage overhead lines
  • Dead-end and angle supports
  • Mountain, rural, urban and sensitive sites
  • Shared support for power, telephone and TV cables

Advantages

  • Lighter than wood or concrete poles: easier transport, lifting and erection
  • Fireproof and immune to termites, rodents and woodpeckers
  • No chemical wood treatment
  • Deform without sudden failure in an accident, limiting the domino effect
  • No maintenance beyond regular inspection

Options and configurations

  • Vault-type crossarm: two levels, with central arm, horizontal or lattice
  • Single anchor crossarm: 1,800, 2,100 and 2,400 mm spacing
  • Double anchor crossarm: allowable loads per phase by longitudinal and vertical load
  • IACM, IA2T or M2S pole-mounted switches to suit the line design
  • Ladder rungs on request

Documentation

No document online for this product yet. Ask our team for the datasheet.

Request the datasheet

A project to price?

Send us your drawings or specification: our design office sizes the structures and replies with a priced offer.